_ DEC-O-LOG for H7226 _ DOL, H7226-M001, Constant Voltage Conditioner, MAY 87 PROBLEM: Cold solder flow may cause loosening of connectors resulting in high resistance connections, overheating may then result. There is a small potential risk of product damage that dictates the mandatory coding of the FCO. FIELD EFFECTIVITY: Mandatory rework, all variations of the H7226 Constant Voltage Conditioner. Existing inventory has already been reworked by the vendor. This FCO is being released against Jefferson Electric ECO #EC-49865 on file with engineering. This FCO is mandatory and should be installed on all units. QUICK CHECK: Variable tap selection cable (H2) NOT tinned and set screw tight. FCO KIT ORDERING: EQ N/A FA-04763-01 FCO only _ DOL, H7226-S002, Constant Voltage Conditioner, MAR 90 PROBLEM: Wiring on unit main harness may be pinched/twisted in a manner to cause electrical short or voltage present on internal "cage". FIELD EFFECTIVITY: Applies to the following Option/Serial Numbers: H7226-JC (NQF00311 to NQF00340) and H7226-LC (NQF00367 to NQF00385). QUICK CHECK: Serial number on back of cabinet. If serial number falls in the ranges of those above, the unit must be swapped. FCO KIT ORDERING: EQ-01574-01 H7226-JC & FA-04880-01 FA-01574-02 H7226-LC & FA-04880-01 FA-04880-01 FCO Document only